Based on the structure of an imported impingement air blast freezer, the design parameters of the evaporator with aluminum tube and fin were predefined. The refrigerant was R717, and refrigeration capacity was 70kW. Heat transfer coefficient of air and refrigerant were calculated separately, regardless to the influence of dirt in the tube, the method for calculation heat transfer coefficient of this kind of evaporator was gained. By way of the experimental investigation on this type of evaporator, the calculation method was indicated to be reasonable.
參考文獻
相似文獻
引證文獻
引用本文
謝晶,張珍,徐世瓊.上下沖擊式鼓風凍結(jié)裝置傳熱系數(shù)的計算[J].農(nóng)業(yè)機械學報,2008,39(12):102-106.[J]. Transactions of the Chinese Society for Agricultural Machinery,2008,39(12):102-106.